M&M Refrigeration, Inc.

 

Refrigeration Pressure Vessels

Standard Vertical High Pressure Receiver   ·   Standard Horizontal High Pressure Receiver  ·  Standard Vertical Accumulator
Standard Vertical Intercooler  ·  Standard Single Flow Horizontal Surge Drum  ·  Standard Dual Flow Horizontal Surge Drum
Standard Horizontal Recirculator Bare Vessel  ·  Standard Vertical Recirculator Bare Vessel  ·  Back to Main Page

Standard Horizontal Recirculator Bare Vessel




LEGEND
Nozzle Descripition Connection
A Wet Return Stub
B Gas Outlet Stub
C Pump Suction Stub
E Float Column Stub
F Liquid Makeup Stub
G Relief Coupling
H Oil Drain Stub
I Oil Pot Vent Coupling
J Volute Vent Stub
K Liquid By-Pass Stub
M Pump Bleed Stub

 

DIMENSIONS
Model Number A B C D E F G H I J K L M N O P Q Surge Vol.
Cu. Ft.
Wt.
(Lb)
HRC-24-112 5 4 2-1/2" 24" 1-1/4" 1-1/2" 3/4" 2" 3/4" 3/4" 1" 112-1/2" 3/4" 8-1/4" 96" 48" 6" 8.47 1300
HRC-30-115 6 5 3" 30" 1-1/4" 2" 3/4" 2" 3/4" 3/4" 1-1/4" 115-1/2" 3/4" 9-3/4" 96" 48" 8" 15.85 1575
HRC-36-118 6 6 4" 36" 1-1/4" 2" 3/4" 2" 3/4" 3/4" 1-1/4" 118-1/2" 3/4" 11-1/4" 96" 48" 8" 25.45 2525
HRC-42-145 8 6 4" 42" 1-1/4" 2-1/2" 3/4" 2" 3/4" 3/4" 1-1/2" 145-1/2" 3/4" 12-3/4" 120" 60" 10" 44.95 3500
HRC-48-148 8 8 5" 48" 1-1/4" 3" 3/4" 2" 3/4" 3/4" 1-1/2" 148-1/2" 3/4" 14-1/4" 120" 60" 10" 62.22 4915
HRC-54-152 10 8 5" 54" 1-1/4" 3" 3/4" 2" 3/4" 3/4" 1-1/2" 152" 3/4" 16" 120" 60" 10" 82.2 4720
HRC-60-155 10 8 5" 60 1-1/2" 3" 3/4" 2" 3/4" 3/4" 1-1/2" 155" 3/4" 17-1/2" 120" 60" 12" 104.65 6440
HRC-72-161 12 10 6" 72" 1-1/2" 4" 1" 2" 3/4" 3/4" 1-1/2" 161" 3/4" 20-1/2" 120" 60" 14" 158.94 9610
HRC-84-167 12 10 8" 84" 1-1/2" 4" 1" 2" 3/4" 3/4" 2" 167" 3/4" 23-1/2" 120" 60" 16" 225.86 11175
HRC-96-172 14 12 8" 96" 1-1/2" 5" 1" 2" 3/4" 3/4" 2" 172-1/2" 3/4" 26-1/4" 120" 60" 16" 307.15 15990

Notes:
All dimensions and Nozzle sizes are given in inches.
Please consult factory for certified drawings.
Surge volume is the amount of area between normal operating level and high level cutout.
24" thru 48" vessels are designed for 300# DWP -40 +200 Design Temp. Per ASME Section VIII, Division 1
54" and larger vessels are desgned for 250# DWP -40 +200 Design Temp. Per ASME Section VIII, Division 1

 

HORIZONTAL RECIRCULATOR CAPACITIES - OPERATING TEMPERATURE
Model Number TWO STAGE SINGLE STAGE
-50 -40 -30 -20 -20 -10 0 +10 +20 +30 +40
HRC-24-112 49.8 61.7 74.6 88.3 76.8 88.9 101 115 129 141 152
HRC-30-115 79.5 98.4 119 141 123 142 161 183 206 226 243
HRC-36-118 113 140 170 201 175 202 229 262 294 322 346
HRC-42-145 156 194 234 278 241 279 316 361 405 445 477
HRC-48-148 206 256 309 366 319 368 416 476 534 587 629
HRC-54-152 263 326 394 467 406 470 531 608 682 748 802
HRC-60-155 327 405 490 580 505 584 660 755 847 930 997
HRC-72-161 470 582 704 833 725 839 947 1084 1216 1336 1432
HRC-84-167 639 791 957 1132 985 1140 1287 1473 1653 1815 1946
HRC-96-172 833 1031 1248 1477 1284 1486 1679 1922 2156 2368 2539

Notes:
Capacities are given in tons of refrigeration. (R-717)
Two stage capacities are based on +35 deg. F liquid feed temperature
Single stage capacities are based on +95 deg. F liquid feed temperature

Top of Page